4-20 mA Scaling Calculator

Convert between milliamps, percent and engineering units for any range, with the raw PLC count.

Free. No sign-up. Runs entirely in your browser, so nothing you type is uploaded or stored.

Current

12 mA

Percent of span

50 %

Value

5 bar

Raw count

13,824

Formula: value = low + (mA − 4) ÷ 16 × (high − low). Raw ranges differ by card and configuration; check your module's manual.

How to use it

  1. 1Enter the range your transmitter is set to: the value at 4 mA and at 20 mA.
  2. 2Choose which way you are converting, and type the number.
  3. 3Pick your analog card to see the raw count the PLC reads.
  4. 4Below 3.8 mA or above 20.5 mA usually means a fault, not a reading.